Title | Applied Research of the Hygrothermal Behaviour of an Internally Insulated Historic Wall without Vapour Barrier: In Situ Measurements and Dynamic Simulations |
Creator | M. Andreotti, D. Bottino-Leone, M. Calzolari, P. Davoli, L. Dias Pereira, E. Lucchi, A. Troi |
Contributor | N/A |
Subject | The HeLLo project applied research communication output. |
Description | The hygrothermal behaviour of an internally insulated historic wall is still hard to predict, mainly because the physical characteristics of the materials composing the historic wall are unknown. In this study, the hygrothermal assessment of an internally thermal insulated masonry wall of an historic palace located in Ferrara, in Italy, is shown. In situ non-destructive monitoring method is combined with a hygrothermal simulation tool, aiming to better analyse and discuss future refurbishment scenarios. In this context, the original U-value of the wall (not refurbished) is decreased from 1.44 W/m2K to 0.26 W/m2K (10 cm stone wool). Under the site specific conditions of this wall, not reached by the sun or rain, it was verified that even in the absence of vapour barrier, no frost damage is likely to occur and the condensation risk is very limited. Authors proposed further discussion based on simulation. The results showed that the introduction of a second gypsum board to the studied technology compensated such absence, while the reduction of the insulation material thickness provides a reduction of RH peaks in the interstitial area by 1%; this second solution proved to be more efficient, providing a 3% RH reduction and the avoidance of further thermal losses. |
Publisher | MDPI |
Date | July 2020 |
Type | Research document |
Format | PDF 2,3 MB |
Source | https://www.mdpi.com/1996-1073/13/13/3362/htm |
Language | English |
Rights Management | Attribution 4.0 International (CC BY 4.0) Creative Commons |